Product Details


PRODUCT TEST REPORT

  Specification

JKLV WASP 100mm²

Standard

BS 6485

Quantity

96km

Ref.No.

Detection

Standard requirements

Unit

Detection result

Determine

1

AL alloy

1.1

Diameter

4.39±1%

mm

4.39

P

1.2

Number of wire

7


7

P

1.3

Electrical Resistivity

≤0.028264

Ω·mm 2 /m

0.02801

P

1.4

Tensile strength

≥160

Mpa

165

P

2

Twisted conductor

2.1

Conductor diameter

13.17±1%

mm

13.17

P

2.2

DC resistance at 20 ℃

≤0.2702

Ω/km

0.2685

P

2.3

Lay ratio(Outside)

10~14

mm

11

P

2.4

Rated Strength

≥16

kN

17

P

2.5

Direction

Right


Right

P

3

Cable

3.1

Insulating material

PVC


PVC

P

3.2

Nominal Thicknes

1.33

mm

1.42

P

3.3

Minimum Thicknes

1.1

mm

1.25

P

3.4

Approximate diameter of Core

16.0


15.9

P

3.5

Approximate weight of cable

360


380

P

Conclusion

Comply with BS 6485 standard and allow shipment.


PRODUCT TEST REPORT

Specification

JKLHV OAK 100mm²

Standard

BS 6485

Quantity

103km

Ref.No.

Detection

Standard requirements

Unit

Detection result

Determine

1

AL alloy

1.1

Diameter

4.65±1%

mm

4.66

P

1.2

Number of wire

7


7

P

1.3

Electrical Resistivity

≤0.03250

Ω·mm 2 /m

0.03232

P

1.4

Tensile strength

≥295

Mpa

310

P

2

Twisted conductor

2.1

Conductor diameter

13.95±1%

mm

13.96

P

2.2

DC resistance at 20 ℃

≤0.2769

Ω/km

0.2750

P

2.3

Lay ratio(Outside)

10~14

mm

11

P

2.4

Rated Strength

≥35.07

kN

36.8

P

2.5

Direction

Right


Right

P

3

Cable

3.1

Insulating material

PVC


PVC

P

3.2

Nominal Thicknes

1.33

mm

1.45

P

3.3

Minimum Thicknes

1.1

mm

1.23

P

3.4

Approximate diameter of Core

18.0


17.6

P

3.5

Approximate weight of cable

470


450

P

Conclusion

Comply with BS 6485 standard and allow shipment.